Display method |
4-digit 7-segment LED |
Control method |
ON/OFF, P, PI, PD, PID |
Input specification |
Thermocouple: K(CA), J(IC), T(CC), R(PR), S(PR), L(IC)
RTD: DPt100Ω, Cu50Ω |
Sampling cycle |
100ms |
Control output |
Relay(250VAC~ 3A) or SSR drive(12VDC ) [ON/OFF] |
Option output |
Alarm 1/2 |
Power supply |
100-240VAC~ 50/60Hz |
Display accuracy_RTD |
•At room temperature(23ºC ± 5ºC):(PV ± 0.5% or ±1ºC, select the higher one) ± 1-digit
•Out of room temperature range:(PV± 0.5% or ±2ºC, select the higher one)± 1-digit |
Display accuracy_Thermocouple |
•At room temperature(23ºC ± 5ºC):(PV ± 0.5% or ±1ºC, select the higher one) ± 1-digit
•Out of room temperature range:(PV± 0.5% or ±2ºC, select the higher one)± 1-digit |
Hysteresis(adjustable sensitivity) |
1 to 100℃/℉(0.1 to 50.0℃/℉) variable |
Proportional band |
0.1 to 999.9℃/℉ |
Integral time |
0 to 9999 sec |
Derivative time |
0 to 9999 sec |
Control period |
0.5 to 120.0 sec |
Manual reset |
0.0 to 100.0% |
Environment_Ambient temperature |
-10 to 50℃, storage: -20 to 60℃ |
Environment_Ambient humidity |
35 to 85% RH, storage: 35 to 85% RH |
Insulation type |
Double insulation or reinforced insulation(mark: , dielectric strength between the measuring input part and the power part: AC power 2kV, AC/DC Power 1kV) |
Weight |
Approx. 147g(approx. 100g) |