Description

  • Display method : 4-digit 7-segment LED
  • Control method : ON/OFF, P, PI, PD, PID
  • Input specification : Thermocouple: K(CA), J(IC), T(CC), R(PR), S(PR), L(IC)
    RTD: DPt100Ω, Cu50Ω
  • Sampling cycle : 100ms
  • Control output : Relay(250VAC~ 3A) or SSR drive(12VDC ) [ON/OFF]
  • Power supply : 100-240VAC~ 50/60Hz
  • Display method 4-digit 7-segment LED
    Control method ON/OFF, P, PI, PD, PID
    Input specification Thermocouple: K(CA), J(IC), T(CC), R(PR), S(PR), L(IC)
    RTD: DPt100Ω, Cu50Ω
    Sampling cycle 100ms
    Control output Relay(250VAC~ 3A) or SSR drive(12VDC ) [ON/OFF]
    Option output Alarm 1/2
    Power supply 100-240VAC~ 50/60Hz
    Display accuracy_RTD •At room temperature(23ºC ± 5ºC):(PV ± 0.5% or ±1ºC, select the higher one) ± 1-digit
    •Out of room temperature range:(PV± 0.5% or ±2ºC, select the higher one)± 1-digit
    Display accuracy_Thermocouple •At room temperature(23ºC ± 5ºC):(PV ± 0.5% or ±1ºC, select the higher one) ± 1-digit
    •Out of room temperature range:(PV± 0.5% or ±2ºC, select the higher one)± 1-digit
    Hysteresis(adjustable sensitivity) 1 to 100℃/℉(0.1 to 50.0℃/℉) variable
    Proportional band 0.1 to 999.9℃/℉
    Integral time 0 to 9999 sec
    Derivative time 0 to 9999 sec
    Control period 0.5 to 120.0 sec
    Manual reset 0.0 to 100.0%
    Environment_Ambient temperature -10 to 50℃, storage: -20 to 60℃
    Environment_Ambient humidity 35 to 85% RH, storage: 35 to 85% RH
    Insulation type Double insulation or reinforced insulation(mark: , dielectric strength between the measuring input part and the power part: AC power 2kV, AC/DC Power 1kV)
    Weight Approx. 147g(approx. 100g)

Additional information

Weight 1 kg
Dimensions 100 × 100 × 70 cm